Nature of Requirements:
DND - Supply Chiller
W3555-146947
Cond, Anthony A.
Telephone No. - (250) 363-3309
Fax No. - (250) 363-3960
Requirement:
The Department of National Defence has a requirement for a
chiller for shore support for the Canadian west coast submarine
fleet.
Delivery:
CIP (Carriage Insurance Paid), Destination, Victoria, B.C.,
Incoterms 2000 for shipment on or before 28 March 2014.
Background:
Requirement for a fully self-contained de-ionized water chilling
and circulating unit in support of Victoria Class submarines.
Mandatory Standards and Certifications:
- Electrically certified by approved Canadian agency
- Chilled water minimum temperature = 7 deg Celsius
- Flow rate between 20 US gallons per min and 102 US gallons per
minute with de-ionized fluid reservoir
- Pressure head = 166 feet continuous including 2-pump redundancy
- Dimensions must not exceed 120 inches high, 96 inches wide,
180 inches long.
- Weight must not exceed 10,000 pounds including chilled fluid
in the system. Must have fork lift pockets and crane lifting
eyes.
- Cooling capacity must be 25 tons minimum using independently
operable or in tandem redundant air-cooled chillers.
- Chiller must include automatic auxiliary system to mitigate
freeze-up when idling or in use.
- Power requirement: 460 volt, 3-phase, with a full load current
draw of 100 amps. All electrical enclosures must meet NEMA 3R
ratings at a minimum.
Deliverables:
one (1) Chiller.
Sourcing Strategy:
Subject to AIT, WTO and NAFTA.
Delivery Date: Above-mentioned
The Crown retains the right to negotiate with suppliers on any
procurement.